What is Lines or Feeder Protection?

Encyclopedia
09/10/2024 15:44:53


What is Lines or Feeder Protection?


Transmission Line Protection Definition


Transmission line protection is a set of strategies used to detect and isolate faults on power lines, ensuring system stability and reducing damage.


Time Graded Over Current Protection


This may also be referred simply as over-current protection of electrical power transmission line. Let’ discuss different schemes of time graded over current protection.


Protection of Radial Feeder


In radial feeder, the power flows in one direction only, which is from source to load. This type of feeders can easily be protected by using either definite time relays or inverse time relays.


Line Protection by Definite Time Relay


This protection scheme is very simple. Here total line is divided into different sections and each section is provided with definite time relay. The relay nearest to the end of the line has minimum time setting while time setting of other relays successively increased, towards the source.


For example, suppose there is a source at point A, in the figure below


7301408a68fd527a087ca3f80d8e2051.jpeg


At point D the circuit breaker CB-3 is installed with definite time of relay operation 0.5 sec. Successively, at point C another circuit breaker CB-2 is installed with definite time of relay operation 1 sec. The next circuit breaker CB-1 is installed at point B which is nearest of the point A. At point B, the relay is set at time of operation 1.5 sec.


Now, assume a fault occurs at point F. Due to this fault, the faulty current flow through all the current transformers or CTs connected in the line. But as the time of operation of relay at point D is minimum the CB-3, associated with this relay will trip first to isolate the faulty zone from rest part of the line.


 In case due to any reason, CB-3 fails to trip, then next higher timed relay will operate to initiate the associated CB to trip. In this case, CB-2 will trip. If CB-2 also fails to trip, then next circuit breaker i.e. CB-1 will trip to isolate major portion of the line.


Advantages of Definite Time Line Protection


The main advantage of this scheme is simplicity. The second major advantage is, during fault, only nearest CB towards the source from fault point will operate to isolate the specific position of the line.


Disadvantage of Definite Time Line Protection


With many sections in a line, the relay close to the source has a longer delay, which means faults near the source take longer to isolate, potentially causing severe damage.


Over Current Line Protection by Inverse Relay


The drawback as we discussed just in definite time over current protection of transmission line, can easily be overcome by using inverse time relays. In inverse relay the time of operation is inversely proportional to fault current.


In the above figure, overall time setting of relay at point D is minimum and successively this time setting is increased for the relays associated with the points towards the point A.


In case of any fault at point F will obviously trip CB-3 at point D. In failure of opening CB-3, CB-2 will be operated as overall time setting is higher in that relay at point C.


Even though the relay nearest to the source has the longest setting, it will trip faster if a major fault occurs near the source because its operation time is inversely proportional to the fault current.


e9e864a410a39a383b09e255426e701f.jpeg


Over Current Protection of Parallel Feeders


For maintaining stability of the system it is required to feed a load from source by two or more than two feeders in parallel. If fault occurs in any of the feeders, only that faulty feeder should be isolated from the system in order to maintain continuity of supply from source to load. This requirement makes the protection of parallel feeders little bit more complex than simple non direction over current protection of line as in the case of radial feeders. The protection of parallel feeder requires to use directional relays and to grade the time setting of relay for selective tripping.


There are two feeders connected in parallel from source to load. Both of the feeders have non-directional over current relay at source end. These relays should be inverse time relay. Also both of the feeders have directional relay or reverse power relay at their load end. The reverse power relays used here should be instantaneous type. That means these relays should be operated as soon as flow of power in the feeder is reversed. The normal direction of power is from source to load.


Now, suppose a fault occurs at point F, say the fault current is I f.


85f5bb666ecc4b08a484a20b23e47d85.jpeg


This fault will get two parallel paths from source, one through circuit breaker A only and other via CB-B, feeder-2, CB-Q, load bus and CB-P. This is clearly shown in figure below, where IA and IB are current of fault shared by feeder-1 and feeder-2 respectively.


As per Kirchoff’s current law, I A + IB = If.


200e8e499e23fcebe13afa42afccb89a.jpeg


Now, IA is flowing through CB-A, IB is flowing through CB-P. As the direction of flow of CB-P is reversed it will trip instantly. But CB-Q will not trip as flow of current (power) in this circuit breaker is not reversed. As soon as CB-P is tripped, the fault current IB stops flowing through feeder and hence there is no question of further operating of inverse time over current relay. IA still continues to flow even CB-P is tripped. Then because of over current IA, CB-A will trip. In this way the faulty feeder is isolated from system.

 


Differential Pilot Wire Protection


This is simply a differential protection scheme applied to feeders. Several differential schemes are applied for protection of line but Mess Price Voltage balance system and Translay Scheme are most popularly used.


Merz Price Balance System


The working principle of Merz Price Balance system is quite simple. In this scheme of line protection, identical CT is connected to each of the both ends of the line. The polarity of the CTs is same. The secondary of these current transformer and operating coil of two instantaneous relays are formed a closed loop as shown in the figure below. In the loop pilot wire is used to connect both CT secondary and both relay coil as shown.


Now, from the figure it is quite clear that when the system is under normal condition, there would not be any current flowing through the loop as the secondary current of one CT will cancel out secondary current of other CT.


Now, if any fault occurs in the portion of the line between these two CTs, the secondary current of one CT will no longer equal and opposite of secondary current of other CT. Hence there would be a resultant circulating current in the loop.


Due to this circulating current, the coil of both relays will close the trip circuit of associate circuit breaker. Hence, the faulty line will be isolated from both ends.

 

1702beb95fc089b8b8f1cc31c3a1037c.jpeg

 

Master Electrician

Welcome to our electricity community! Established to facilitate the exchange and cooperation in the electricity industry and bridge professionals, enthusiasts, and related enterprises.