Shunt Reactor Definition


A shunt reactor is defined as an electrical device that absorbs reactive power in power systems.


Reactance Calculation


The reactance of a shunt reactor can be calculated as it is nearly equal to its impedance.


V-I Characteristics


The simple formula of impedance in ohm is

 

Where, V is voltage in volt and I is current in ampere.

 

8a786ba4de3022dee5f55a4e8c73af49.jpeg

 

But in the case of shunt reactor, impedance Z = reactance X.Where, V is applied voltage across the winding of the reactor and I is the corresponding current through it.


As the V-I characteristic of the reactor is linear, reactance of the reactor winding remains fixed for any applied voltage below the maximum rated value.


In the case of reactance measurement of three phase shunt reactor, we use sinusoidal three phase supply voltage of power frequency (50 Hz) as test voltage. We connect three supply phases to three terminals of the reactor winding as shown. Before that we should make sure that the neutral terminal of the winding is properly earthed.

 

1e7aba2e7f50bacc920885f1cfd1c7d8.jpeg


Three-Phase Measurement


But in the case of shunt reactor, impedance Z = reactance X.


Where, V is applied voltage across the winding of the reactor and I is the corresponding current through it.


As the V-I characteristic of the reactor is linear, reactance of the reactor winding remains fixed for any applied voltage below the maximum rated value.


In the case of reactance measurement of three phase shunt reactor, we use sinusoidal three phase supply voltage of power frequency (50 Hz) as test voltage. We connect three supply phases to three terminals of the reactor winding as shown. Before that we should make sure that the neutral terminal of the winding is properly earthed.

 

31600733ed104e88e9b16e9a54b16570.jpeg

7874e6ad2aa83d5ec34afd90cea46fb0.jpeg


Zero Sequence Reactance


For three phase reactors with magnetic iron path for zero sequence flux, zero sequence reactance may be measured as follows.


In this method, short the three terminals of the reactor and apply a single-phase supply between the common phase terminal and the neutral terminal. Measure the current through the common path, then divide the applied single-phase voltage by this current. Multiply the result by three to obtain the zero sequence reactance per phase.

 

ce855c8d4ca3e9077000b626f31f8df8.jpeg 