• PVC insulated and PVC sheathed power cable
PVC insulated and PVC sheathed power cable
discuss personally
Basic info
Brand Wone
Series VV series
Product Detail

PVC insulated and PVC sheathed power cable

1.Application

It is used as power distribution and transmission system at rated voltage 0.6/1KV, AC50Hz.

2.Performance

a.The long-time working temperature of cable should not be higher than 70.

b.When core is in short-circuit(max 5s), the temperature should not exceed 160.

c.While installation the ambient temperature should not be lower than 0 , and the bending radius should not be less than 10 times of outer diameter of cable.

3.Model, name and application型号.png

4.Structure and size

VV,VLV,ZRVV,ZRVLV

0.6/1kv PVC Insulated PVC Sheathed Flame Retardant or Non-flame Retardant power CableVV1.pngVLV2.pngZRVV3.pngZRVLV4.pngVV5.pngVV6.pngVV7.pngVV8.png

VV22,VLV22,ZRVV22,ZRVLV22

0.6/1kv PVC Insulated steel Armoured PVC Sheathed Flame Retardant or Non-flame Retardant PowerVV22.pngVV22 2.pngVV22 3.pngVV22 4.pngVV22 5.pngVV22 6.png

VV22 7.png

VV22 8.png

5.Installation

a.Installation

   1The installation temperature should not over 20 , lf the ambient temperature is lower than 0 ,the cable should be preheated;

   2The bending radius of cable should not less than 5 times;

   3After installation, the cable should have voltage test for 15min. 3.5kv d.c.

b.In air laying

   1As the single core cable laying in parallel, the distance between the cable:center is 2 times(for cables,which cross sectional area of conductor 185mm2)and 90mm(for cables,which cross sectional     area of conductor 240mm2);

   2Ambient temperature: 30 ;

   3)Max.temperature of conductor: 70 ;

   4)Modified coefficient of current carrying capacity for ambient temperature:

温度倍率.png

c.Direct in ground laying

   1)When the single core cables are installed separately, the distance between the cable: center is 2 times of the cable diameter;

   2)Ambient temperature: 25;

   3)Max.temperature of conductor: 70;

   4)Soil thermour resistivity: 1.0 .m/w;

   5)Depth: 0.7m;

   6) Modified coefficient of current carrying capacity for ambient temperature:温度倍率2.png

d.Short ciruit ratings

温度倍率3.png

6.Current Carrying Capacity

VV,ZRVV

0.6/1kV Copper Conductor PVC Insulated PVC sheathed Flame Retardant & Non-Flame Retardant Power Cable Installed in Air for Long Term and Continuously Load载流表1.png

VLV,ZRVLV

0.6/1kV Aluminum Conductor PVC Insulated PVC sheathed Flame Retardant or Non-flame Retardant Power Cable Installed in Air for Long Termand Continuously Load载流表2.png

VV22,ZRVV22

0.6/1kV Copper Conductor PVC Insulated PVC Sheathed Flame Retardant & Non-flame Retardant Power Cable Installed Direct in Ground for Long Term Continuously Load载流表3.png

VLV22 , ZRVLV22

0.6/1kV Aluminum Conductor PVC Insulated PVC Sheathed Flame Retardant & Non-flame Retardant power Cable Installed Direct in Ground for Long Term and Continuously Load载流表4.png