Brand | ROCKWILL |
Model NO. | 40.5KV 72.5KV 126KV 252KVseries high voltage earthing switch |
Rated voltage | 40.5kV |
Rated normal current | |
Series | JW |
Description
JW6/8 series high voltage earthing switch is composed of three single poles and operating mechanism. Each single pole consists of a base, a pillar insulator and a conducting rod. The conductive rod is installed on the base, and the static contact is installed on the top of the pillar insulator.
The operating mechanism drives the conductive rod to rotate upward from the horizontal position through the transmission element, and is stuck or inserted into the static contact to realize the closing of the ground switch, and the opening process is the opposite.
Main Features
The product structure is simple and reasonable, easy to assemble, transport, install and debug.
The conductive rod is made of high-strength alloy profiles with good electrical conductivity, high mechanical strength, light weight, strong anti-corrosion ability and long service life.
Technical parameter
Specifications |
Unit |
Value |
|||||||
Model |
JW6-40.5 |
JW6-72.5 |
JW6-126 |
JW6-252 |
JW8-363 |
JW8-550 |
JW8-800 |
||
Rated voltage |
kV |
40.5 |
72.5 |
126 |
252 |
363 |
550 |
800 |
|
Rated frequency |
HZ |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
1min power frequency withstand voltage (r.m.s) |
kV |
95 |
160 |
230 |
460 |
510 |
740 |
960 |
|
Lightning impulse withstand voltage (peak 1.2/50us) |
kV |
185 |
380 |
550 |
1050 |
1175 |
1675 |
2100 |
|
Rated operating impulse withstand voltage(peak 250/2500μs) |
kV |
\ |
\ |
\ |
\ |
950 |
1300 |
1550 |
|
Rated short-time withstand current (r.m.s) |
kA |
40 |
40 |
40 |
50 |
63 |
63 |
63 |
|
Rated peak withstand time |
kA |
100 |
100 |
100 |
125 |
160 |
160 |
170 |
|
Rated short-circuit withstand time |
S |
4 |
4 |
3 |
3 |
3 |
3 |
3 |
|
Wiring terminal static mechanical load |
Longitudinal |
N |
800 |
800 |
1250 |
2000 |
2000 |
4000 |
4000 |
Horizontal |
500 |
500 |
750 |
1500 |
1500 |
2000 |
3000 |
||
Vertical |
750 |
750 |
1000 |
1250 |
1500 |
1500 |
2000 |
||
Operational altitude |
m |
≤2000 |
≤2000 |
≤2000 |
≤2000 |
≤2000 |
≤1000 |
≤2000 |
|
Operating pollution class |
Class |
AG5 |
AG5 |
AG5 |
AG5 |
AG5 |
AG5 |
AG3 |
|
Mechanical life |
Times |
10K |
10K |
5K |
10K |
5K |
5K |
3K |
|
Radio interference level |
uV |
≤500 |
≤500 |
≤500 |
≤500 |
≤500 |
≤500 |
≤2000 |
|
The switching induced current capacity of the earthing switch |
Electromagnetic induction current |
A |
6 |
6 |
50/100 |
80/160 |
80/400 |
80/400 |
80/400 |
Electromagnetic induction voltage |
kV |
100 |
100 |
0.5/6 |
1.4/15 |
2/35 |
2/35 |
2/35 |
|
Electrostatic induction current |
A |
6 |
6 |
0.4/5 |
1.25/10 |
2/35 |
2/50 |
3/50 |
|
Electrostatic induction voltage |
kV |
2 |
2 |
3/6 |
5/15 |
8/50 |
8/50 |
12/50 |