Brand | ROCKWILL |
Model NO. | GW46 125KV 252KV 550KV series disconnector |
Rated voltage | 252KV |
Rated normal current | 3150A |
Series | GW |
Description
GW46 series disconnector adopts single-column double-arm folding structure, expands the clamp range of vertical fracture disconnector, enhances the stability of opening and closing operation, and improves the flow ability. The ground switch has the characteristics of simple structure, reliable operation and easy operation.
Main Features
Beautiful appearance, strong flow ability, high insulation level, long mechanical life.
Strong anti-corrosion ability, the conductive system is made of aluminum alloy material, the base is welded and hot-dip galvanized, the transmission system is made of stainless steel material or cast aluminum parts, the transmission part of the conductive system is completely sealed, so that the product as a whole has good anti-corrosion.
Clamp range is large, suitable for large-span soft bus, but also suitable for pipe bus.
Adapt to large areas of wind and sand.
Technical parameter
Specifications |
Unit |
Value |
|||
Model |
GW46-126 |
GW46-252 |
GW46-550 |
||
Rated voltage |
kV |
125 |
252 |
550 |
|
Rated current |
A |
3150 |
3150/4000/5000 |
4000/5000 |
|
Rated frequency |
HZ |
50 |
50 |
50 |
|
1min power frequency withstand voltage (r.m.s) |
Phase to phase/ to earth |
kV |
230 |
460 |
740 |
Across isolating distance |
kV |
230(+73) |
460(+146) |
740(+315) |
|
Lightning impulse withstand voltage (peak 1.2/50us) |
Phase to phase/ to earth |
kV |
550 |
1050 |
1675 |
Across isolating distance |
kV |
550(+103) |
1050(+206) |
1675(+450) |
|
Rated operating impulse withstand voltage(peak 250/2500μs) |
Phase to phase/to earth |
kV |
\ |
\ |
1300 |
Across isolating distance |
kV |
\ |
\ |
1175(+450) |
|
Rated short-time withstand current (r.m.s) |
kA |
40 |
50/63 |
63 |
|
Rated peak withstand time |
kA |
100 |
125/160 |
170 |
|
Rated short-circuit withstand time |
S |
3 |
3 |
3 |
|
Wiring terminal static mechanical load |
Longitudinal |
N |
1250 |
2000 |
4000 |
Horizontal |
750 |
1500 |
2000 |
||
Vertical |
100 |
1250 |
1500 |
||
Operational altitude |
m |
≤2000 |
≤2000 |
≤1000 |
|
Operating pollution class |
Class |
AG5 |
AG5 |
AG5 |
|
Mechanical life |
Times |
10K |
10K |
10K |
|
Radio interference level |
uV |
≤500 |
≤500 |
≤500 |
|
bus-transfer current switching by disconnector |
bus-transfer current |
A |
1600 |
1600 |
1600 |
bus-transfer voltage |
V |
100 |
300 |
400 |
|
disconnector switch capacitive open current |
A |
1 |
1 |
2 |
|
disconnector switch inductive open current |
A |
0.5 |
0.5 |
1 |
|
The switching induced current capacity of the earthing switch |
Electromagnetic induction current |
A |
50 |
80/160 |
80 |
Electromagnetic induction voltage |
kV |
0.5 |
1.4/15 |
2 |
|
Electrostatic induction current |
A |
0.4 |
1.25/10 |
2 |
|
Electrostatic induction voltage |
kV |
3 |
5/15 |
8 |