Brand | Wone |
Model NO. | PX three-phase power frequency inverter |
Mounting type | Wall-mounted |
Rated Output Rating | 8kW |
Input Voltage | DC48V |
Series | PX series |
Peculiarity:
♦ Dual phase inverter, AC three-phase input and output.
♦ Backward compatible with traditional lead batteries, colloidal batteries.
♦ Can be customized adjustment management battery charging and discharging strategy.
♦ Modular design, easy maintenance.
Technical parameter:
Product model |
PX-8k |
PX-10k |
PX-12k |
||
Rated power |
5kW |
10kW |
12kW |
||
Standard battery unit voltage |
48VDC |
48VDC |
48VDC |
||
Standard Voltage range |
42-60VDC |
42-60VDC |
42-60VDC |
||
Rated PV charging voltage |
360VDC |
||||
MPPT tracking range |
120-450V |
||||
MPPTMPPT track number |
2 |
||||
Grid input voltage (phase voltage) |
170~280V(UPS)/120~280V(INV) |
||||
Input frequency |
45~65Hz |
||||
Maximum grid input current |
160A single |
200A single |
240A single |
||
Maximum PV input current |
180A single |
220A single |
260A single |
||
Maximum PV input Power |
5500W X2 |
7500W X2 |
9000W X2 |
||
Ac access mode |
Firing line*3+Neutral line |
||||
inverse |
Rated output voltage |
230V*3+N |
The output electric energy standard is applicable to most countries or regions such as Chinese mainland, Hong Kong, Macao, North Korea, Australia, South Asia, the Middle East, Europe, Africa, South America, etc., and customers in non-above regions can customize according to the customer's local electric energy standard. |
||
Rated output frequency |
48~52HZ (58~62HZ) |
||||
System efficiency |
86~94% |
||||
Grid following |
Rated output voltage |
Follow the grid |
|||
Rated output frequency |
Follow the grid |
||||
System efficiency |
99% |
||||
Installation mode |
wall-mounted |
||||
Battery no load loss |
≤1% |
||||
Power grid no load loss |
≤0.5% |
||||
Cooling mode |
Forced air cooling |
||||
Operating environment |
Temperature: -10~40℃ Humidity: 20~95RH% |
||||
Maximum working altitude |
2000m(> 2000m load reduction required) |
||||
Protection |
Battery under (over) voltage protection/overload protection/over temperature protection/short circuit protection |
||||
Class of protection |
IP20 |
||||
Size(mm) |
620*445*130 |
||||
Operation mode |
Mains priority/PV priority/battery priority |