Brand | ROCKWILL |
Model NO. | 126KV 252KV 363KV 420KV 550KV series disconnector |
Rated voltage | 420KV |
Rated normal current | 3150A |
Series | GW |
Description
GW16 series disconnector adopts single-column single-arm vertical telescopic structure, which is mainly composed of base, insulator, conductive system, operating mechanism, etc. The disconnector is operated by CJ11 motor operating mechanism for opening and closing. The attached ground switch is mainly composed of ground switch system and operating mechanism, and each group of ground switches is operated by a CJ11 motor operating mechanism for opening and closing.
Main Features
Simple and compact structure, small footprint.
Strong product flow capacity, long mechanical life.
Optimized spring design, light and smooth operation.
High seismic performance, can resist nine degrees of earthquake intensity.
The layout is flexible, convenient for users to choose.
Technical parameter
Specifications |
Unit |
Value |
|||||
Model |
GW16/16B-126 |
GW16B-252 |
GW16B-363 |
GW16B-420 |
GW16B-550 |
||
Rated voltage |
kV |
126 |
252 |
363 |
420 |
550 |
|
Rated current |
A |
2500/3150 |
3150/5000 |
3150/5000 |
3150 |
3150/4000 |
|
Rated frequency |
HZ |
50 |
50 |
50/60 |
50 |
50 |
|
1min power frequency withstand voltage (r.m.s) |
Phase to phase/ to earth |
kV |
230 |
460 |
510 |
520 |
740 |
Across isolating distance |
kV |
230(+73) |
460(+146) |
510(+210) |
610 |
740(+315) |
|
Lightning impulse withstand voltage (peak 1.2/50us) |
Phase to phase/ to earth |
kV |
550 |
1050 |
1175 |
1425 |
1675 |
Across isolating distance |
kV |
550(+103) |
1050(+206) |
1175(+295) |
1425(+240) |
1675(+450) |
|
Rated operating impulse withstand voltage(peak 250/2500μs) |
Phase to phase/to earth |
kV |
\ |
\ |
950 |
1050 |
1300 |
Across isolating distance |
kV |
\ |
\ |
850(+295) |
900(+345) |
1175(+450) |
|
Rated short-time withstand current (r.m.s) |
kA |
40 |
50/63 |
50/63 |
50 |
50/63 |
|
Rated peak withstand time |
kA |
100 |
135/160 |
125/160 |
130 |
125/160 |
|
Rated short-circuit withstand time |
S |
3 |
3 |
3 |
3 |
3 |
|
Wiring terminal static mechanical load |
Longitudinal |
N |
1250 |
2000 |
2000 |
4000 |
4000 |
Horizontal |
750 |
1500 |
1500 |
1600 |
2000 |
||
Vertical |
1000 |
1250 |
1500 |
1500 |
1500 |
||
Operational altitude |
m |
≤2000 |
≤2000 |
≤2000 |
≤1000 |
≤1000 |
|
Operating pollution class |
Class |
AG5 |
AG5 |
AG3/AG5 |
AG5 |
AG3 |
|
Mechanical life |
Times |
5K |
10K |
5K/3K |
10K |
10K |
|
Radio interference level |
uV |
≤500 |
≤500 |
≤500 |
≤500 |
≤500 |
|
bus-transfer current switching by disconnector |
bus-transfer current |
A |
1600 |
1600 |
1600 |
1600 |
1600 |
bus-transfer voltage |
V |
100 |
300 |
300 |
300 |
400 |
|
disconnector switch capacitive open current |
A |
1 |
1 |
2 |
1 |
2 |
|
disconnector switch inductive open current |
A |
0.5 |
0.5 |
1 |
0.5 |
1 |
|
The switching induced current capacity of the earthing switch |
Electromagnetic induction current |
A |
50/80 |
80/160 |
80 |
80 |
80 |
Electromagnetic induction voltage |
kV |
0.5/2 |
1.4/15 |
2 |
2 |
2 |
|
Electrostatic induction current |
A |
0.4/2 |
1.25/10 |
1.25 |
1.25 |
2 |
|
Electrostatic induction voltage |
kV |
3/6 |
5/15 |
5 |
5 |
8 |